Performance data for Trox
Package with performance data for active beams from Trox.
Name | Description |
---|---|
DID632A_nozzleH_length6ft_cooling | Performance data for Trox DID 632A for cooling mode |
DID632A_nozzleH_length6ft_heating | Performance data for Trox DID 632A for heating mode |
Performance data for Trox DID 632A for cooling mode
Performance data for Trox active beam for cooling mode.
Extends from Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Generic (Generic data record for active beam).
Type | Name | Default | Description |
---|---|---|---|
Nominal condition | |||
MassFlowRate | mAir_flow_nominal | 0.0792 | Nominal air mass flow rate per beam [kg/s] |
MassFlowRate | mWat_flow_nominal | 0.094 | Nominal water mass flow rate per beam [kg/s] |
PressureDifference | dpWat_nominal | 10000 | Water-side nominal pressure drop per beam [Pa] |
PressureDifference | dpAir_nominal | 100 | Air-side nominal pressure drop [Pa] |
TemperatureDifference | dT_nominal | -10 | Nominal temperature difference water inlet minus room air [K] |
HeatFlowRate | Q_flow_nominal | -1092 | Nominal capacity per beam [W] |
Performance data for Trox DID 632A for heating mode
Performance data for Trox active beam for heating mode.
Extends from Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Generic (Generic data record for active beam).
Type | Name | Default | Description |
---|---|---|---|
Nominal condition | |||
MassFlowRate | mAir_flow_nominal | 0.0792 | Nominal air mass flow rate per beam [kg/s] |
MassFlowRate | mWat_flow_nominal | 0.094 | Nominal water mass flow rate per beam [kg/s] |
PressureDifference | dpWat_nominal | 10000 | Water-side nominal pressure drop per beam [Pa] |
PressureDifference | dpAir_nominal | 100 | Air-side nominal pressure drop [Pa] |
TemperatureDifference | dT_nominal | 27.8 | Nominal temperature difference water inlet minus room air [K] |
HeatFlowRate | Q_flow_nominal | 2832 | Nominal capacity per beam [W] |